Repository logo
 

A study of high voltage direct current conductor corona in a purpose built corona cage.

dc.contributor.advisorIjumba, Nelson Mutatina.
dc.contributor.advisorBritten, Anthony C.
dc.contributor.authorSibilant, Gary Charles.
dc.date.accessioned2012-02-21T06:46:03Z
dc.date.available2012-02-21T06:46:03Z
dc.date.created2003
dc.date.issued2003
dc.descriptionThesis (M.Sc.)-University of Durban-Westville, 2003.en
dc.description.abstractThe main aim of this study was concerned with the design and commissioning of a corona cage, which could be used under Direct Current (DC) conditions. The cage was designed based on empirical formulas and equations as well as electric field simulations. The designed cage was then fabricated. The commissioning of the cage was undertaken in the High Voltage Direct Current (HVDC) laboratory at the University of Durban - Westville (UDW). Tests to determine the effects of a silicone coating as well as wind on the corona performance of conductors were undertaken. The tests were done in order to determine ways of improving the corona performance of conductors under HVDC potential. The tests were carried out using various conductor surface conditions. The wind tests were made possible by using a powerful fan. A silicone coating was also used to determine the effects that it would have in mitigation of corona activity on HVDC conductors. The conductors were tested without the coating, with half of their length coated and then fully coated. Results showed that the effect of wind on corona generation in a corona cage is minimal. The effect of the silicone coating was that it increased the corona currents measured in the corona cage. The conductors with no coating generated the lowest currents, the half coated conductors generated the second highest measured currents and the fully coated conductors generated the most corona. Analysis of the increased currents showed that the increase in corona currents due to the silicone coating could be attributed to three factors. Firstly the coating caused an increase in conductor to cage capacitance. Secondly, partial discharges could have occurred in the silicone due to microscopic air particles and lastly, the increase in corona currents could be ascribed to the effect of the boundary conditions on the boundary between the conductor and the coating.en
dc.identifier.urihttp://hdl.handle.net/10413/5063
dc.language.isoenen
dc.subjectHigh voltage direct current.en
dc.subjectElectrical engineering.en
dc.subjectTheses--Electrical engineering.en
dc.titleA study of high voltage direct current conductor corona in a purpose built corona cage.en
dc.typeThesisen

Files

Original bundle

Now showing 1 - 1 of 1
Loading...
Thumbnail Image
Name:
Sibilant_G_C_2003.pdf
Size:
2.23 MB
Format:
Adobe Portable Document Format
Description:
Thesis.

License bundle

Now showing 1 - 1 of 1
No Thumbnail Available
Name:
license.txt
Size:
1.64 KB
Format:
Item-specific license agreed upon to submission
Description: